To send your information to Tsubaki, press this button
Features:
  • Communication function allows central monitoring
  • The 4 to 20 mA output allows communication to a central control, or as input to controls that operators monitor and adjust to maintain production
  • Panel mounting with remote display option
  • Both Under current and Over current monitoring
  • Inverter compatible from 20 to 200 Hz
  • Locked rotor protection
  • Phase imbalance protection
  • Phase loss protection
  • Thermal overload protection
  • Can be used with single-phased motors
  • Multiple operations can be linked together and monitored from one location
Unit of Measure

Specifications

Type

N/A All-in One Type

Max Amperage

N/A 60

Amperage Range

N/A 10 to 60 A

230 Volt Motor HP

N/A 5 to 25 hp

460 Volt Motor HP

N/A 10 to 50 hp

Mounting Type

N/A Panel mounting with remote display option

Electrical Life

N/A Activation 100,000times at rated load cycles

Ambient Humidity

N/A 30 to 85%RH (No dew condensation) %

Start Time [Min]

N/A 0.2 s

Start Time [Max]

N/A 12.0 s

Shock Time [Min]

N/A 0.2 s

Shock Time [Max]

N/A 0.5 s

Operation Frequency

N/A 20 to 200 Hz

Maximum Motor Voltage

N/A AC600V 50/60Hz

Operation Power

N/A 100 to 240 VAC +/- 10%, 50/60 Hz

Current detection accuracy

N/A +/- 5% (In case of commercial power source)

Time detection accuracy

N/A +/- 5 %

Under current

N/A 0.2 to 5 s

Lock when starting up

N/A Set at 2 to 8 times of overcurrent setting value (OFF: No action) Trip after Star t time + 0.2s when star ting up.

Lock when operating

N/A Set at 1.5 to 8 times of overcurrent setting value (OFF: No action), trip at 0.2 to 5s.

Phase-reversal

N/A Trip within 0.15s, (OFF: No action)

Phase loss

N/A Trip at 0.5 to 5s (OFF: No action)

Imbalance

N/A Trip at 1 to 10s (OFF: No action) when setting at 10 to 50%

Alarm

N/A Output when A, F and H are set (OFF: No action)

Running hour

N/A Trip when 10 to 9990hr is set (OFF: No action)

Fail-safe

N/A Activated when setting ON (Conducting normally: Excited, Trip: Non-excited)

Rated load

N/A 3A, 250VAC

Minimum allowable load

N/A DC24V, 4mA

Contact arrangement

N/A OC:1c,AL/UC/TO:1a

Self-holding

N/A E-r: Manual release or reset of power source, H-r: Only manual release

Auto-reset

N/A A-r: Auto-reset and set the return time at 0.2s to 20min

Analog output

N/A Analog output 4 to 20mA DC Output (OFF: No action) Allowable load resistance: 100O and below

Communication output

N/A RS485/Modbus

Insulation between case and circuit

N/A DC500V, 10MO

Dielectric strength voltage between housing-circuit

N/A 2000VAC 60Hz 1min.

Dielectric strength voltage between relay contacts

N/A 1000VAC 60Hz 1min.

Location

N/A Indoors, where it will not get wet

Ambient temperature

N/A -20 to 60 ºC

Ambient humidity

N/A 30 to 85%RH (no dew condensation)

Altitude

N/A 2000 m

Atmosphere

N/A No corrosive gas, oil-mist or dust

Vibration

N/A 5.9 m/s²

Power consumption

N/A 7.0 VA

Weight

N/A 0.30 kg